System: | | 12kV | 17.5kV | 24kV |
Rated Voltage | kV | 12 | 17.5 | 24 |
Lightning Impulse withstand voltage | kV | 75 | 95 | 125 |
Power frequency withstand voltage | kV | 28 | 38 | 50 |
Rated frequency | Hz | 50 | 50 | 50 |
Internal arc class | | AFL 25kA-1s |
Loss of service continuity category | | LSC2B |
Partition class | | PM |
Earthing circuit | kA-s | 25 - 3 |
Compartment circuit-breaker/cable | | Interlock-controlled |
Compartment busbar | | Tool-based/non-accessible |
Degree of protection HV compartments(Optional) | | IP4X |
Degree of protection LV compartment | | IP3XD |
Temperature classification | | Minus 5 °C indoor |
Busbar system: | | |
Rated normal current | A | 2000 |
Rated short-time withstand current | kA-s | 25 - 3 |
Rated peak withstand current | kA | 63 |
Circuit-breaker - incoming feeder and sectionalizer: | | |
Rated normal current | A | 1250 - 1600 - 2000 |
Rated short-circuit breaking current | kA | 25 |
Rated short-circuit making current | kA | 63 |
Rated short-time withstand current | kA-s | 25 - 3 |
Circuit-breaker – outgoing feeder: | | |
Rated normal current | A | 630 - 800 |
Rated short-circuit breaking current | kA | 25 |
Rated short-circuit making current | kA | 63 |
Rated short-time withstand current | kA-s | 25 - 3 |
Class | | E2, C2 |
Operating cycles at short-circuit current | | 100 |
Single capacitor bank switching | A | 400 |
Mechanism: | | |
Rated operating sequence | A | O - 0.3s – CO - 15s - CO |
Class | | M2 |
Opening time | ms | 35 |
DC component | % | 35 |
Closing time | ms | 70 |
Number of operations actuator | | 30.000 |
Number of operations interrupter | | 30.000 |
Auxiliary voltage | V | 24, 48, 60,110,220 DC/ 110/230 AC |
Mechanism change-over switch | | |
Opening time | s | 24 |
Closing time | s | 24 |
Number of operations change-over switch | | 1.000 |
Class | | M0 |